EHWB – Electric (25–5,000 kW)
-
Features
-
Technical data
-
Contact us
Key Features
EHWB boilers are designed and manufactured for a system in which heat is transferred to the water by immersion heating elements.
An EHWB boiler is a cylindrical vessel fitted with suitable connection flanges for the heating elements. A vertical cylindrical design is used for small capacities, and a horizontal cylindrical design for large capacities.
The thermal load of the heating elements is selected to be less than 10 W/cm².
Heating elements with multiple flange connections are used so that the boiler can continue to operate if any heater fails.
Hinged covers are provided so that the heaters can be reached easily. Maintenance and replacement of the heaters can therefore be carried out readily.
The boiler design is prepared in accordance with the PED2014/68 directive and bears the CE mark.
Where applicable, the standards EN12953, EN13445 and EN1090 are observed.
Akkaya Isı Makinaları A.Ş. holds ISO3834 and ISO9001 quality system certificates.
System Components
High-efficiency cylindrical hot water / high-temperature hot water boiler
Heating elements
Boiler hot water flow / return valves
Boiler filling and drain valves
Boiler air vent valve
Boiler thermometer
PLC-based control panel with touch screen and remote access
Safety valve
Pressure gauge and three-way connection valve
Pressure switch
Pressure transmitter
Boiler temperature sensor (operation)
Boiler temperature switch (safety)
Circulation pump group, expansion tank, rapid water heating tank, accumulation tank
| EHWB series | EHWB25 | EHWB50 | EHWB100 | EHWB120 | EHWB150 | EHWB200 | EHWB250 | EHWB300 | EHWB350 | EHWB400 | EHWB450 | EHWB500 | EHWB600 | EHWB700 | EHWB800 | EHWB900 | EHWB1000 | EHWB1250 | EHWB1500 | EHWB2000 | EHWB2500 | EHWB3000 | EHWB3500 | EHWB4000 | EHWB4500 | EHWB5000 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Maximum heat output (kW) | 25 | 50 | 100 | 120 | 150 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 600 | 700 | 800 | 900 | 1.000 | 1.250 | 1.500 | 2.000 | 2.500 | 3.000 | 3.500 | 4.000 | 4.500 | 5.000 |
| Minimum water flow (for ΔT 20°C) (m3/h) | 1 | 2 | 4 | 5 | 6 | 9 | 11 | 13 | 15 | 17 | 19 | 22 | 26 | 30 | 34 | 39 | 43 | 54 | 65 | 86 | 108 | 129 | 151 | 172 | 194 | 215 |
| Length (mm) | 1500 | 1500 | 1600 | 1700 | 1700 | 1800 | 2300 | 2000 | 2300 | 2500 | 2600 | 2800 | 2800 | 3000 | 3200 | 2900 | 3100 | 3600 | 3300 | 3500 | 4000 | 4500 | 4600 | 5000 | 5400 | 4900 |
| Width (mm) | 500 | 700 | 800 | 800 | 900 | 1000 | 1000 | 1100 | 1100 | 1200 | 1200 | 1200 | 1400 | 1400 | 1400 | 1600 | 1600 | 1600 | 1800 | 2000 | 2000 | 2200 | 2200 | 2200 | 2200 | 2400 |
| Height (mm) | 700 | 900 | 1000 | 1000 | 1100 | 1200 | 1200 | 1300 | 1300 | 1400 | 1400 | 1400 | 1600 | 1600 | 1600 | 1800 | 1800 | 1800 | 2000 | 2200 | 2200 | 2400 | 2400 | 2400 | 2400 | 2600 |
| **Weight (kg) | 210 | 320 | 440 | 450 | 560 | 680 | 800 | 900 | 910 | 1200 | 1250 | 1350 | 1550 | 1700 | 1950 | 2050 | 2200 | 2500 | 2700 | 3600 | 4300 | 4800 | 5000 | 5400 | 6100 | 6200 |
Tabloyu yana kaydırın
In industrial heat,